CNC Electric – YCB9RL-100 RCCB Electromagnetic (3-Phase MCCB, 80A)

SKU: ELC1603

$22.01

The YCB9RL-100 RCCB Electromagnetic is a 3-phase molded case circuit breaker (MCCB) designed for overload, short-circuit, and earth fault protection, widely used in residential, non-residential, energy, and industrial infrastructure.

Categories: ,

This MCCB provides overload protection, short-circuit protection, and control functions, with instantaneous tripping classified as Type B (3–5 In), Type C (5–10 In), and Type D (10–20 In).

It ensures protection against sinusoidal alternating earth fault currents, indirect and direct contacts, and fire hazards caused by insulation faults.

Built to IEC/EN 61008-1 standards, it uses electromagnetic sensing of leakage currents. The device has a rated current of 80A, a rated voltage of 230V, a breaking capacity of 6000A, and operates at 50Hz. Rated sensitivity is 0.3A (300mA), ensuring reliable residual current protection.

It offers a mechanical life of 8000 operations and an electrical life of 4000 operations, with IP20 protection degree. Operating temperature ranges from -5°C to +40°C (daily average ≤35°C), with storage between -25°C and +70°C.

Connections are supported for cables, pin-type busbars, and U-type busbars, with terminal sizes up to 25/35 mm² for cables and 10/16 mm² for busbars.

Tightening torque is 2.5 N·m (22 in-lbs). Mounting is via DIN rail EN 60715 (35 mm) with a fast clip device, and connections can be made from top and bottom.

 

TECHNICAL DETAILS:

 

Specification Details
Model/Series YCB9RL-100 RCCB Electromagnetic
Type 3-Phase MCCB / RCCB
Rated Current (In) 80 A
Poles 2, 4
Rated Voltage (Ue) 230 V
Insulation Voltage (Ui) 500 V
Rated Frequency 50 Hz
Breaking Capacity (Inc/Ic) 6000 A
Impulse Withstand Voltage (Uimp)  (1 min) 2.5 kV
Dielectric Strength 6000 V
Rated Sensitivity (An) 0.3 A (300 mA)
Residual Making/Breaking Capacity (IΔm) 1000 A (for 80A model)
Protection Functions Overload, short-circuit, earth fault, control
Instantaneous Tripping Types B (3–5 In), C (5–10 In), D (10–20 In)
Pollution Degree 2
Electrical Life 4000 operations
Mechanical Life 8000 operations
Protection Degree IP20
Ambient Temperature -5°C to +40°C (daily avg ≤35°C)
Storage Temperature -25°C to +70°C
Terminal Connection Cable / Pin-type busbar / U-type busbar
Terminal Size (Cable) 25/35 mm²
Terminal Size (Busbar) 10/16 mm²
Tightening Torque 2.5 N·m (22 in-lbs)
Mounting DIN rail EN 60715 (35 mm), fast clip
Connection Top and bottom
Applications Residential, non-residential, energy industry, infrastructure